| MODEL | YFP-85W2 | YFP-136W2 | YFP-204W2 | YFP-289W2 | |
| COOLING CAP | Btu/h | 15000 | 25000 | 38000 | 52000 | |
| W | 4500 | 7200 | 11000 | 15300 | |
| HEATING CAP | Btu/h | 23000 | 38000 | 56000 | 78000 | |
| W | 6800 | 11000 | 16500 | 23000 | |
| POWER INPUT | W | 70 | 130 | 190 | 290 | |
| MOTOR CURRENT | A | 0.3 | 0.56 | 0.82 | 1.25 | |
| POWER SUPPLY | V/P/HZ | 220V/50HZ | |
| AIR FLOW | m3/h | 850 | 1360 | 2040 | 2890 | |
| NOISE LEVEL | dB(A) | 43 | 45 | 49 | 52 | |
| OPERATION CONTROL | REMOTE CONTROL OR WIRE WALL PAD | |
| CHAMBER MACHINE SIZE(L×P×H) | mm | 1125×590×290 | 1700×590×290 | |
| PANEL COVER L×P×H) | mm | 1245×680×45 | 1920×680×45 | |
| PANEL WEIGHT | kg | 9 | 12 | |
| WEIGHT | kg | 45 | 60 | |
| | | | | | | | |
| 1.Outlet air static pressure is 0pa. |
| 2.27degrees DB/19.5degrees WB entering air temperature,7degrees entering water and 12degrees leaving water temperature. |
| 3.20degrees DB entering air temperature,60degrees entering water and 50degrees leaving water temperture. |
two-way Cassetee fan coil unit has been presented above, want more similar products, please click two-way fan coil unit,two-way Cassetee coil unit.
Category:
Water Systematic/Fan Coil Units
Related Category:
Fluorine Systematic Series